Click to enlarge image
|
Origin |
China |
Model Number |
BD-12/1250 |
Brand Name |
BGE |
Circuit-breaker used glass vacuum tube , we have ISO9000 , "3C" certificate and so on Vacuum Tube main techincal parameter
|
Parameter name
|
Unit
|
Value
|
|
Rated voltage
|
kV
|
12
|
|
Rated normal current
|
A
|
1250,1600
|
|
Rated frequency
|
Hz
|
50
|
|
Rated short-circuit breaking current
|
kA
|
20,25,31.5
|
|
Rated short-circuit making current
|
kA
|
50,63
|
|
Rated peak withstand current
|
A
|
50,63
|
|
Rated short-time withstand current
|
kA
|
20,25,31.5
|
|
Rated short-circuit continuous time
|
S
|
4
|
|
Rated single capacitor unit breaking current
|
A
|
630
|
|
Rated back to back capacitor unit breaking current
|
A
|
400
|
|
Rated short-time (1 min) frequency withstand voltage
|
kV
|
42
|
|
Rated contact pressure time-limit loop resistive
|
µΩ
|
≤30
|
|
Rated short-circuit breaking current breaking times
|
|
30
|
|
Rated lightning impulse withstand voltage
|
V
|
75
|
|
Mechanical life
|
|
10000
|
|
Contact automatic
|
N
|
120±50
|
|
Force required to hold contacts open at full stroke
|
N
|
200±50
|
|
Contact-wear allowance thickness
|
mm
|
3
|
|
Internal gas pressure
|
Pa
|
≤1.33×10-3
|
|
Shelf life
|
|
20
|
|
|
Delivery lead time |
according to clients |
Supply ability |
10000 Piece/Pieces / Month |
|
|
| |
|
|
|